EL2808
EL2808 | HD EtherCAT Terminal, 8-channel digital output 24 V DC, 0.5 A
The EL2808 digital output terminal connects the binary control signals from the automation device on to the actuators at the process level with electrical isolation. The EL2808 is protected against polarity reversal and processes load currents with outputs protected against overload and short-circuit. The EtherCAT Terminal contains eight channels, consisting of a signal output and 0 V DC. The signal states are displayed by LEDs. The power contacts are looped through.
Connection technology: | 2-wire |
Number of outputs: | 8 |
Rated load voltage: | 24 V DC (-15 %/+20 %) |
Load type: | ohmic, inductive, lamp load |
Distributed clocks: | – |
Max. output current: | 0.5 A (short-circuit-proof) per channel |
Short circuit current: | typ. < 2 A |
Reverse voltage protection: | yes |
Breaking energy: | < 150 mJ/channel |
Switching times: | typ. TON: 60 µs, typ. TOFF: 300 µs |
Current consumption E-bus: | typ. 110 mA |
Electrical isolation: | 500 V (E-bus/field potential) |
Current consumption power contacts: | typ. 15 mA + load |
Bit width in the process image: | 8 outputs |
Configuration: | no address or configuration setting |
Conductor types: | solid wire, stranded wire and ferrule |
Conductor connection: | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver |
Rated cross-section: | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² |
Weight: | approx. 65 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Approvals: | CE, UL, Ex |
ТН ВЭД: | |
Страна происхождения: | |
EAN: | |
Вес: | 0,00 kg |
Длина: | 0,00 m |
Ширина: | 0,00 m |
Высота: | 0,00 m |