Article image 401600

Rechner Sensors 401600

KAS-40-30-N, ATEX

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Capacitive Sensors. Series 40 – NAMUR EN 60947-5-6. Housing Ø 30 mm. For use in areas with the risk of gas explosion, zone 0. Housing material: PA / PPO. Sensing distance 3…15 mm adjustable

Pliki do pobrania

Parametry techniczne

Thread / Process connection: Ø 30 mm
Housing material active surface: PPO
Housing material: PA / PPO
Housing material lid: PA
Electrical version: 2-Leiter DC
Permitted residual ripple max.: 5%
Frequency of operating cycles max.: 50 Hz
LEDdisplay: Gelb
Protective circuit: Eingebaut
Degree of protection IEC 60529: IP 67 (mit versiegelter Potentiometerschraube)
Norm: EN 60947-5-6
Selfinductance (L): 0,2 mH
Selfcapacitance (C): 250 nF
Operating current active surface free: < typ. 1,5 mA
Operating current active surface covered: > typ. 2,5 mA
Sensing dinstance Sn: 10 mm
Operating distance min. / max. adjustable: 3…15 mm
Operating voltage: 5…15 V DC, Ui = 15 V DC
Permitted ambient temperature min.: -20 °C
Permitted ambient temperature max.: +70 °C
Installation: Bündig
Output function: NAMUR
Cable length: 2 m
Connection: PUR-Kabel, 2 x 0,75 mm²
CE: JA
RoHS: JA
UL CSA certification: JA
ATEX product marking gas: Ex II 1G Ex ia Ex IIC T1 – T6 Ga
Certified Zones ATEX: 1G
IECEX product marking gas: Ex ia IIC T1 – T6 Ga
MTTF: 913,33 Jahre
WHG certification: Auf Anfrage

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m