UBC10.241-N1
DC-UPS control unit
Compact and easy to install. Longest buffer time in class. Easy battery access. Stable output voltage in buffer mode. Superior battery management for longest battery life. Temperature compensated battery charging. Comprehensive diagnostics and monitoring functions. Replace battery signal included. Electronically overload and short circuit protected. 50% power reserves. Selectable buffer time limiter
DC-Input Voltage: | DC 24V |
Int. Current consumption (incl. Charging Current): | 1.3A |
Nominal Voltage: | 24Vdc |
Output Current: | 15A |
Output Power: | 360W |
Storage element: | built-in lead acid battery |
Allowed Battery Size: | 12V, 5Ah |
Temperature Tracking of the End-of-Charge Voltage: | automatically with temp. Sensor |
Size (WxHxD): | 123mm x 124mm x 119mm |
Weight per Piece (excluding packing): | 850g |
Operat. Temperature Range: | 0°C ... +40°C |
Mounting Method: | Din-Rail |
MTBF SN 29500 @ 40°C (h): | 886.000h |
Connection method: | Spring terminals |
I2): | 15A/360W resp. 30A/720W for up to 5s |
ECCN: | |
Kraj pochodzenia: | |
EAN: | |
Waga: | 0,00 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |