2907161
TRIO-UPS-2G/1AC/24DC/10
Width: | 68 mm |
Height: | 130 mm |
Depth: | 160 mm |
Width with alternative assembly: | 160 mm |
Height with alternative assembly: | 130 mm |
Depth with alternative assembly: | 68 mm |
Installation distance right/left: | 0 mm / 0 mm |
Installation distance top/bottom: | 50 mm / 50 mm |
Degree of protection: | IP20 |
Inflammability class in acc. with UL 94 (housing / terminal blocks): | V0 |
Ambient temperature (operation): | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested): | -40 °C |
Ambient temperature (storage/transport): | -40 °C ... 85 °C |
Max. permissible relative humidity (operation): | ≤ 93 % (At +25°C, non-condensing) |
Climatic class: | 3K3 (in acc. with EN 60721) |
Degree of pollution: | 2 |
Installation height: | ≤ 4000 m (> 2000 m, observe derating) |
AC input voltage range: | 100 V AC ... 240 V AC -15 % ... +10 % |
Inrush current limiting/I²t: | < 0.2 A2s |
Mains buffering time: | ≥ 25 ms (120 V AC) |
Typical response time: | 200 ms |
Input fuse, integrated: | 6.3 A (slow-blow, internal) |
Nominal output voltage: | 24 V DC |
Setting range of the output voltage (USet): | 24 V DC ... 28 V DC (> 24 V constant capacity) |
Nominal output current (IN): | 10 A |
Dynamic Boost (IDyn.Boost): | 15 A |
Derating: | > 60 °C (2.5%/K of POut nom.) |
Control deviation: | < 0.55 % (Static load change 10 % ... 90 %) |
Maximum power dissipation in no-load condition: | < 3 W (230 V AC) |
Efficiency: | typ. 90 % (120 V AC) |
Residual ripple: | < 20 mV |
Connection in parallel: | yes, with diode module uncoupled |
Surge protection against internal surge voltages: | < 30 V DC |
Feedback voltage resistance: | ≤ 35 V DC |
Net weight: | 1.34 kg |
Insulation voltage input/output: | 4 kV AC (type test) |
Protection class: | I |
MTBF (IEC 61709, SN 29500): | > 2007013 h (230 V AC, at 25 °C) |
Mounting position: | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions: | alignable: horizontally 0 mm, vertically 50 mm |
Connection method: | Push-in connection |
Conductor cross section solid min.: | 0.2 mm² |
Conductor cross section solid max.: | 4 mm² |
Conductor cross section flexible min.: | 0.2 mm² |
Conductor cross section flexible max.: | 2.5 mm² |
Conductor cross section AWG min.: | 24 |
Conductor cross section AWG max.: | 12 |
Stripping length: | 10 mm |
Connection method: | Push-in connection |
Conductor cross section solid min.: | 0.2 mm² |
Conductor cross section solid max.: | 4 mm² |
Conductor cross section flexible min.: | 0.2 mm² |
Conductor cross section flexible max.: | 2.5 mm² |
Conductor cross section AWG min.: | 24 |
Conductor cross section AWG max.: | 12 |
Stripping length: | 10 mm |
Connection method: | Push-in connection |
Conductor cross section solid min.: | 0.2 mm² |
Conductor cross section solid max.: | 1.5 mm² |
Conductor cross section flexible min.: | 0.2 mm² |
Conductor cross section flexible max.: | 1.5 mm² |
Conductor cross section AWG min.: | 24 |
Conductor cross section AWG max.: | 16 |
Stripping length: | 8 mm |
Charge characteristic curve: | IU0U |
Charge current: | 0.2 A ... 3 A (-25 °C ... 60 °C) |
EMC requirements for noise immunity: | EN 61000-6-1 |
EMC requirements for noise emission: | EN 61000-6-3 |
Standard - safety for equipment for measurement, control, and laboratory use: | IEC 61010-1 |
Standard – Safety extra-low voltage: | IEC 61010 (SELV) / (PELV) |
Standard - Safe isolation: | DIN VDE 0100-410 |
Standard - power supply devices for low voltage with DC output: | EN 61204-3 |
UL approvals: | UL Listed UL 61010 |
Electromagnetic compatibility: | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive: | Conformance with Low Voltage Directive 2014/35/EC |
Conducted noise emission: | EN 61000-6-3 (Class B) |
Noise emission: | EN 61000-6-3 (Class B) |
DNV GL conducted interference: | Class B |
Additional text: | Area power distribution |
DNV GL noise radiation: | Class B |
Additional text: | Bridge and deck area |
Electrostatic discharge: | EN 61000-4-2 |
Contact discharge: | 6 kV (Test Level 4) |
Discharge in air: | 8 kV (Test Level 4) |
Electromagnetic HF field: | EN 61000-4-3 |
Frequency range: | 80 MHz ... 6 GHz |
Test field strength: | 10 V/m (Test Level 3) |
Comments: | Criterion A |
Fast transients (burst): | EN 61000-4-4 |
Input: | 4 kV (Test Level 4 - asymmetrical) |
Output: | 2 kV (Test Level 3 - asymmetrical) |
Signal: | 2 kV (Test Level 4 - asymmetrical) |
Comments: | Criterion A |
Surge voltage load (surge): | EN 61000-4-5 |
Input: | 2 kV (Test Level 3 - symmetrical) |
Output: | 1 kV (Test Level 1 - symmetrical) |
Signal: | 1 kV (Test Level 2 - asymmetrical) |
Comments: | Criterion A |
Conducted interference: | EN 61000-4-6 |
I/O/S: | asymmetrical |
Frequency range: | 0.15 MHz ... 80 MHz |
Voltage: | 10 V (Test Level 3) |
Comments: | Criterion A |
Attenuated sinusoidal oscillations (ring wave): | EN 61000-4-12 |
Comments: | Criterion A |
Criterion A: | Normal operating behavior within the specified limits. |
Criterion B: | Temporary impairment to operational behavior that is corrected by the device itself. |
REACh SVHC: | Lead 7439-92-1 |
eCl@ss 10.0.1: | 27040705 |
eCl@ss 9.0: | 27040705 |
ETIM 6.0: | EC000382 |
ETIM 7.0: | EC000382 |
ECCN: | |
Kraj pochodzenia: | CN |
EAN: | |
Waga: | 1,70 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |