2320283
QUINT4-UPS/1AC/1AC/1KVA
Width: | 290 mm |
Height: | 130 mm |
Depth: | 125 mm |
Installation distance right/left: | 5 mm / 5 mm |
Installation distance top/bottom: | 50 mm / 50 mm |
Degree of protection: | IP20 |
Ambient temperature (operation): | -25 °C ... 60 °C (> 50 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport): | -40 °C ... 85 °C (with charged energy storage device) |
Max. permissible relative humidity (operation): | ≤ 95 % |
Climatic class: | 3K3 (EN 60721) |
Installation height: | ≤ 3000 m (> 2000 m, observe derating) |
Nominal input voltage: | 100 V AC -10 % / +20 % |
Input voltage range: | 90 V AC ... 264 V AC |
AC frequency range: | 45 Hz ... 65 Hz |
Buffer period: | 1 h (38 AH) |
Permissible backup fuse: | B16 230 V AC |
Power factor (cos phi): | 0.9 |
Nominal output voltage: | 100 V AC |
Nominal output current (IN): | 7.8 A (100 V AC) |
POWER BOOST (IBoost): | 13 A (120 V AC) |
Derating: | > 50 °C ... 60 °C (2.5%/K) |
Connection in parallel: | Yes, 2 |
Connection in series: | No |
Maximum power dissipation in no-load condition: | typ. 17 W (120 V AC) |
Net weight: | 5 kg |
Efficiency: | > 92 % (120 V AC) |
MTBF (IEC 61709, SN 29500): | 217546 h (230 V AC, at 40 °C) |
Degree of protection: | IP20 |
Protection class: | I |
Connection method: | Screw connection |
Conductor cross section solid min.: | 0.2 mm² |
Conductor cross section solid max.: | 6 mm² |
Conductor cross section flexible min.: | 0.2 mm² |
Conductor cross section flexible max.: | 4 mm² |
Conductor cross section AWG min.: | 30 |
Conductor cross section AWG max.: | 10 |
Stripping length: | 8 mm |
Connection method: | Screw connection |
Conductor cross section solid min.: | 0.2 mm² |
Conductor cross section solid max.: | 6 mm² |
Conductor cross section flexible min.: | 0.2 mm² |
Conductor cross section flexible max.: | 4 mm² |
Conductor cross section AWG min.: | 30 |
Conductor cross section AWG max.: | 10 |
Stripping length: | 8 mm |
Connection method: | Screw connection |
Conductor cross section solid min.: | 0.2 mm² |
Conductor cross section solid max.: | 2.5 mm² |
Conductor cross section flexible min.: | 0.2 mm² |
Conductor cross section flexible max.: | 2.5 mm² |
Conductor cross section AWG min.: | 30 |
Conductor cross section AWG max.: | 12 |
Stripping length: | 8 mm |
Standard designation: | Uninterruptible power supply systems |
Standards/regulations: | EN 62040-1 |
Electromagnetic compatibility: | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive: | Conformance with Low Voltage Directive 2014/35/EC |
Electrostatic discharge: | EN 61000-4-2 |
Contact discharge: | ± 6 kV |
Discharge in air: | ± 8 kV |
Electromagnetic HF field: | EN 61000-4-3 |
Frequency range: | 80 MHz ... 6 GHz |
Test field strength: | 10 V/m |
Comments: | Criterion A |
Fast transients (burst): | EN 61000-4-4 |
Input: | ± 2 kV |
Output: | ± 2 kV |
Signal: | ± 2 kV |
Comments: | Criterion A (B for USB) |
Surge voltage load (surge): | EN 61000-4-5 |
Signal: | 1 kV (asymmetrical) |
Comments: | Criterion A |
Conducted interference: | EN 61000-4-6 |
Frequency range: | 0.15 MHz ... 80 MHz |
Voltage: | 10 V |
Comments: | Criterion A |
Power frequency magnetic field: | EN 61000-4-8 |
Frequency: | 50 Hz |
Test field strength: | 100 A/m |
Comments: | Criterion A |
Criterion A: | Normal operating behavior within the specified limits. |
Criterion B: | Temporary impairment to operational behavior that is corrected by the device itself. |
REACh SVHC: | Lead 7439-92-1 |
eCl@ss 10.0.1: | 27040705 |
eCl@ss 5.1: | 27040603 |
eCl@ss 6.0: | 27040600 |
eCl@ss 7.0: | 27040602 |
eCl@ss 8.0: | 27040602 |
eCl@ss 9.0: | 27040705 |
ETIM 5.0: | EC000382 |
ETIM 6.0: | EC000382 |
ETIM 7.0: | EC000382 |
ECCN: | |
Kraj pochodzenia: | DE |
EAN: | |
Waga: | 5,53 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |