269780
VAA-4E4A-KE5-ZEJQ/R
AS-Interface sensor/actuator module
Cabinet module. 4 inputs and 4 relay outputsfa. The AS-Interface connecting module VAA-4E4A-KE5-ZEJQ/R-KRO is a switch cabinet module with 4 inputs and 4 relay contact outputs. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping onto the 35 mm DIN rail in compliance with EN 50022. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+ and AS-i-, two connections are available in each case; these connections are bridged in the terminal block. In case of i-, terminals 5 and 6 as well as 7 and 8 are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The supply to the inputs and the connected sensors can be fed either from the internal supply of the module from the AS-Interface or via an external UEXT voltage source. A switch located on the side of the module changes the source. The internal input supply is displayed via the INT LED. The relevant IN and OUT LEDs display the current switching status of the inputs and outputs. Notes:. The device is equipped with a communication monitor, which deactivates the outputs if the AS-Interface does not communicate with the module for more than 40 ms. The communication monitor can be deactivated via the parameter P0. Filters that suppress pulses with a duration of 2 ms or less at the inputs can be connected via the parameter P1. Parameter P2 activates the AS-Interface synchronous mode. Installation, Commissioning, and Maintenance:. Install the device in a closed electrical plant where only electricians or persons with appropriate electrical training have access. The relevant laws, guidelines, and standards that apply for the application or intended use must be observed. The device must be installed in a switch cabinet or switch box that meets degree of protection IP54 as a minimum. Additional requirements for the AS-Interface power supply:. If voltages that are not in accordance with PELV/SELV are connected to the relay contact outputs, then it must be ensured that the AS-Interface supply voltage does not exceed 36 V, even in the event of a fault. Daisy-Chaining Devices:. Insulation to the outer surfaces of the housing: Basic insulation in accordance with EN 60664-1. To provide reliable and double insulation, devices in the direct vicinity must have basic insulation as a minimum.
Slave type: | Standard slave |
AS-Interface specification: | V3.0 |
Required master specification: | ≥ V2.0 |
UL File Number: | E223772 |
MTBF: | 224 a |
LED FAULT: | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
LED INT: | Internal input supply active; LED green |
LED PWR: | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
LED IN: | switching state (input); 4 LED yellow |
LED OUT: | Switching state (output); 4 LED yellow |
Auxiliary voltage (input): | 12 ... 30 V DC PELV |
Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
Rated operating current: | ≤ 35 mA (without sensors) / max. 230 mA |
Surge protection: | O1 ... O4: Over voltage category II UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV) |
Number/Type: | 4 inputs for 3-wire sensors (PNP), DC |
Supply: | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
Voltage: | 21 ... 31 V DC (INT) |
Current loading capacity: | ≤ 150 mA, overload- and short-circuit protected (INT) |
Input current: | ≤ 5.6 mA (max.) |
Switching point: | according to DIN EN 61131-2 (type 1) |
: 0 (unattenuated): | ≤ 0.5 mA |
: 1 (attenuated): | ≥ 2 mA |
Signal delay: | < 1 ms (input/AS-Interface) |
Number/Type: | 4 relay outputs, normally open |
Supply: | none |
Nominal load: Per contact: | 2 A/30 VDC; 2 A/250 VAC For more information, see the "Galvanic Isolation" section |
Nominal load: Per module: | 8 A |
Control circuit: | ≤ 11 mA per relay (from AS-Interface) |
Switching delay: | < 10 ms (AS-Interface/contact) |
Usage category: | DC-13 and AC-14 |
Switching: Mechanical: | 5 x 107 |
Switching: Electrical: | 2 x 105 (250 VAC, 2 A, cos φ = 0.4) |
Input/Output: | safe isolation, Rated insulation voltage 252 Veff |
Input/AS-Interface: | Switch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff |
Output/Output: | Basic insulation, rated insulation voltage 250 Veff, in phase |
Output/AS-Interface: | safe isolation, Rated insulation voltage 252 Veff |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Low voltage: Directive 2006/95/EC: | EN 60664-1:2007 |
Galvanic isolation: | EN 60664-1:2007 |
Degree of protection: | EN 60529:2000 |
Fieldbus standard: | EN 62026-2:2013 |
Electrical safety: | IEC 61140:2009 |
Input: | EN 61131-2:2004 |
Emitted interference: | EN 61000-6-4:2007 |
AS-Interface: | EN 62026-2:2013 |
Noise immunity: | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013 |
Profile: | S-7.0 |
IO code: | 7 |
ID code: | 0 |
ID1 code: | F |
ID2 code: | E |
Data bits (function via AS-Interface): | input output |
Low voltage: D0: | IN1 O1 |
Low voltage: D1: | IN2 O2 |
Low voltage: D2: | IN3 O3 |
Low voltage: D3: | IN4 O4 |
Parameter bits (programmable via AS-i): | function |
Low voltage: P0: | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
Low voltage: P1: | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
Low voltage: P2: | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
Low voltage: P3: | not used |
Ambient temperature: | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity: | 85 % , noncondensing |
Climatic conditions: | For indoor use only |
Altitude: | ≤ 2000 m above MSL |
Shock and impact resistance: | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
Vibration resistance: | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Pollution degree: | 2 |
Degree of protection: | IP20 Installation in an enclosure with a minimum protection class of IP54 required |
Connection: | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
Material: Housing: | PA 66-FR |
Mass: | 125 g |
Mounting: | DIN mounting rail |
ECCN: | |
Kraj pochodzenia: | Singapur |
EAN: | 4050143046560 |
Waga: | 0,16 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |