IFT259
Inductive full-metal sensor. IFB3005QBPKG/AM/P/US-104
Robust, high-quality stainless steel design. Compact housing for use where space is restricted. Large operating temperature range up to 100 °C. Easy connection via the tried and tested M12 connector
Electrical design: | PNP |
Output function: | normally open |
Sensing range [mm]: | 5 |
Dimensions [mm]: | M12 x 1 / L = 45 |
Special feature: | Gold-plated contacts; Increased sensing range; Full-metal housing |
Application: | constant cleaning with aggressive cleaning agents; regular cleaning processes |
Pressure rating [bar]: | 100 |
Note on pressure rating: | sensing face |
Operating voltage [V]: | 10...30 DC |
Current consumption [mA]: | 20 |
Protection class: | III |
Reverse polarity protection: | yes |
Electrical design: | PNP |
Output function: | normally open |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 100 |
Switching frequency DC [Hz]: | 250 |
Short-circuit protection: | yes |
Overload protection: | yes |
Sensing range [mm]: | 5 |
Real sensing range Sr [mm]: | 5; (± 10 %) |
Operating distance [mm]: | 0...4.05 |
Increased sensing range: | yes |
Correction factor: | steel: 1 / stainless steel: 1 / brass: 0.3 / aluminium: 0.3 / copper: 0.2 |
Hysteresis [% of Sr]: | 3...15 |
Switch point drift [%]: | -10...10 |
Ambient temperature [°C]: | 0...100 |
Protection: | IP 65; IP 66; IP 67; IP 68; IP 69K |
EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 10 V EN 55011 class B |
EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV |
EN 61000-4-6 HF conducted: | 10 V |
EN 55011: | class B |
Impact resistance: | 1 J |
Vibration resistance: | EN 60068-2-6 Fc 20 g (10...3000 Hz) / 50 sweep cycles per frequency; 1 octave per minute in 3 axes |
EN 60068-2-6 Fc: | 20 g (10...3000 Hz) / 50 sweep cycles per frequency; 1 octave per minute in 3 axes |
Shock resistance: | EN 60068-2-27 Ea 100 g 11 ms half-sine; 3 shocks each in every direction of the 3 coordinate axes |
EN 60068-2-27 Ea: | 100 g 11 ms half-sine; 3 shocks each in every direction of the 3 coordinate axes |
Continuous shock resistance: | EN 60068-2-27 40 g 6 ms; 4000 shocks each in every direction of the 3 coordinate axes |
EN 60068-2-27: | 40 g 6 ms; 4000 shocks each in every direction of the 3 coordinate axes |
Fast temperature change: | EN 60068-2-14 Nc TA = 0°C; TB = 100°C; t1 = 30 min; t2 = < 10 s 50 cycles |
EN 60068-2-14 Nc: | TA = 0°C; TB = 100°C; t1 = 30 min; t2 = < 10 s 50 cycles |
MTTF [years]: | 1386 |
UL approval: | Ta 0...70 °C Enclosure type Type 1 voltage supply Unlimited Voltage UL Approval no. A012 File number UL E174191 |
Ta: | 0...70 °C |
Enclosure type: | Type 1 |
voltage supply: | Unlimited Voltage |
UL Approval no.: | A012 |
File number UL: | E174191 |
Weight [g]: | 24.7 |
Mounting: | quasi flush |
Dimensions [mm]: | M12 x 1 / L = 45 |
Thread designation: | M12 x 1 |
Materials: | stainless steel (1.4404 / 316L); sensing face: stainless steel (1.4404 / 316L); LED window: PEI; lock nuts: stainless steel (1.4404 / 316L) |
Tightening torque [Nm]: | 15 |
Length [mm]: | 45 |
Full-metal housing: | yes |
Display: | switching status 4 x LED, yellow |
switching status: | 4 x LED, yellow |
Accessories (supplied): | lock nuts: 2 |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Kraj pochodzenia: | DE |
EAN: | |
Waga: | 0,02 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |