Article image 125277

Eaton 125277

SPX015A1-5A4N1

Variable frequency drive, 600 V AC, 3-phase, 15 kW, IP21, Radio interference suppression filter, OLED display, FR6

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Alternate Catalog No. SPX015A1-5A4N1. EL-Nummer (Norway). 4100128. Variable frequency drive, Part group reference (e.g. DIL): SPX, Rated operational voltage: Ue = 600 V AC, 3-phase, 690 V AC, 3-phase, Output voltage with Ve: U2 = 600 V AC, 3-phase, 690 V AC, 3-phase, Mains voltage (50/60Hz): ULN = 525 (-15%) - 690 (±10%) V, Rated operational current At 150% overload: Ie = 18 A, Rated operational current At 110% overload: Ie = 22 A, Note: Overload cycle for 60 s every 600 s, Assigned motor rating Note: For AC motors with internal and external ventilation with 50 Hz / 60 Hz, Overload cycle for 60 s every 600 s, at 690 V, 50 Hz, Assigned motor rating 150 % Overload: P = 15 kW, 110 % Overload: P = 18.5 kW, 150 % Overload: IM = 17 A, 110 % Overload: IM = 20.9 A, Assigned motor rating Note: at 690 V, 60 Hz, Assigned motor rating 150 % Overload: P = 15 HP, 110 % Overload: P = 20 HP, Assigned motor rating 150 % Overload: IM = 15 A, 110 % Overload: IM = 19 A, Degree of Protection: IP21, Fieldbus connection (optional): PROFIBUS-DP, LonWorks, CANopen®, DeviceNet, Modbus-TCP, BACnet/IP, Fitted with: Radio interference suppression filter, OLED display, DC link choke, Frame size: FR6, Standards: Specification for general requirements: IEC/EN 61800-2, EMC requirements: IEC/EN 61800-3, Safety requirements: IEC/EN 61800-5-1

Parametry logistyczne

ECCN:
Kraj pochodzenia: FI
EAN:
Waga: 18,60 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m