Article image KL1814

Beckhoff KL1814

KL1814 | HD Bus Terminal, 4-channel digital input 24 V DC, 3-wire connection

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The KL1814 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation device. The Bus Terminal contains four channels, consisting of a signal input, 24 V DC and 0 V. The signal states are displayed by LEDs. The power contacts are looped through. The reference ground for all inputs is the 0 V power contact. The wires can be connected without tools in the case of solid wires using a direct plug-in technique.

Parametry techniczne

Connection technology: 3-wire
Specification: EN 61131-2, type 1/3
Number of inputs: 4
Nominal voltage: 24 V DC (-15 %/+20 %)
“0“ signal voltage: -3…+5 V (EN 61131-2, type 1/3)
“1“ signal voltage: 11…30 V (EN 61131-2, type 3)
Input filter: typ. 0.2 ms
Input current: typ. 3 mA (EN 61131-2, type 3)
Current consumption K-bus: typ. 10 mA
Current consumption power contacts: typ. 1 mA + load
Electrical isolation: 500 V (K-bus/field potential)
Bit width in the process image: 4 inputs
Configuration: no address or configuration setting
Conductor types: solid wire, stranded wire and ferrule
Conductor connection: solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver
Rated cross-section: solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm²
Weight: approx. 60 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable (see documentation)
Approvals: CE, UL, Ex, GL

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m