EPP1004-0061
EPP1004-0061 | 4-channel digital input 24 V DC, 3.0 ms
The EPP1004-0061 EtherCAT P Box with digital inputs acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the controller. The state of the signals is indicated by light emitting diodes. The signals are connected via M8 screw type connectors.
Specification: | EN 61131-2, type 1/3 |
Nominal input voltage: | 24 V DC (-15 %/+20 %) |
“1” signal voltage: | 11…30 V (EN 61131-2, type 3) |
“0” signal voltage: | -3…+5 V (EN 61131-2, type 3) |
Input current: | typ. 3 mA (EN 61131-2, type 3) |
Number of inputs: | 4 |
Input filter: | 3.0 ms |
Input connections: | M8, screw type |
Sensor supply: | from control voltage, max. 0.5 A, short-circuit proof in total |
Protocol: | EtherCAT |
Bus interface: | 2 x M8 socket, shielded, screw type, EtherCAT-P-coded |
Distributed clocks: | – |
Power supply connection: | not necessary |
Bit width in the process image: | 4 inputs |
Current consumption from US: | typ. 100 mA |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals/markings: | CE, UL |
ECCN: | |
Kraj pochodzenia: | |
EAN: | |
Waga: | 0,00 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |