Article image EL2819

Beckhoff EL2819

EL2819 | HD EtherCAT Terminal, 16-channel digital output 24 V DC, 0.5 A, with diagnostics

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The EL2819 EtherCAT Terminal has 16 digital output channels for the switching of 24 V loads up to 0.5 A. The integrated diagnostics can be evaluated by the controller and indicated by the LEDs. Overtemperature and the lack of a voltage supply to the terminal are supplied as diagnostic information. Moreover, each of the channels can signal e.g. a short circuit. The switching state and any error of the output are indicated by the LED. Maintenance of the application is simplified by the diagnostic function. The power contacts are connected through; reference ground of the outputs is the 0 V power contact. The outputs are electrically isolated from the fieldbus side.

Parametry techniczne

Connection technology: 1-wire
Number of outputs: 16
Nominal voltage: 24 V DC (-15 %/+20 %)
Load type: ohmic, inductive, lamp load
Distributed clocks:
Max. output current: 0.5 A (short-circuit proof) per channel
Output stage: push (high-side switch)
Short-circuit current: typ. < 1 A
Reverse voltage protection: yes
Breaking energy: < 150 mJ/channel
Current consumption E-bus: typ. 90 mA
Electrical isolation: 500 V (E-bus/field potential)
Current consumption power contacts: typ. 50 mA + load
Bit width in the process image: 16 bit output and diagnostics
Conductor types: solid wire, stranded wire and ferrule
Conductor connection: solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver
Rated cross-section: solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm²
Special features: diagnostics via process data and LED: overtemperature, PowerFail, short circuit (per channel)
Weight: approx. 70 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/see documentation
Approvals/markings: CE, UL, ATEX
Ex-Marking: II 3 G Ex nA IIC T4 Gc

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m