EL1052
EL1052 | 2-channel digital input terminal NAMUR
The EL1052 digital input terminal acquires signals from NAMUR field devices according to IEC 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.
Technology: | NAMUR |
Specification: | NAMUR DC switching amplifier (IEC 60947-5-6) |
Signal type: | binary, current input for NAMUR sensors |
Number of inputs: | 2 |
Connection technology: | 2-wire |
Open circuit voltage: | typ. 8.2 V DC |
“0” signal current: | ≤ 1.2 mA |
“1” signal current: | ≥ 2.1 mA |
Switching hysteresis: | typ. 350 µA |
Short-circuit current: | typ. 7.8 mA |
Fault detection: | I ≤ 200 µA (cable break), I ≥ 7.0 mA (short circuit) |
Max. switching frequency: | 5 kHz (duty factor 50 %) |
Internal resistance: | according to I/V curve IEC 60947-5-6 |
Distributed clocks: | – |
Supply voltage electronics: | 24 V DC (via power contacts) |
Current consumption E-bus: | typ. 40 mA |
Current consumption power contacts: | typ. 20 mA + load |
Electrical isolation: | 500 V (E-bus/field potential) |
Special features: | integrated reverse polarity protection |
Weight: | approx. 60 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all ESxxxx terminals |
Approvals/markings: | CE, UL, ATEX, IECEx |
ECCN: | |
Kraj pochodzenia: | |
EAN: | |
Waga: | 0,00 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |