Article image UB20.241

Puls UB20.241

DC-UPS control unit

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

No change in output voltage in battery mode, selectable output voltages in battery mode. 1-Battery-Concept each 12V battery is charged and, monitored separately for longest battery life. Precise battery charging by using a temperature sensor. Battery size selector for small or large batteries. 50% BonusPower®, 30A for up to 4s. High breaking capacity for branch protectors. Smart battery diagnostics and monitoring functions

Parámetros técnicos

DC-Input Voltage: DC 24V
Int. Current consumption (incl. Charging Current): 1,8/3,5A
Nominal Voltage: 24Vdc
Output Current: 25A
Output Power: 600W
Storage element: external lead acid battery
Allowed Battery Size: 24V, 3.9 to 40Ah
Temperature Tracking of the End-of-Charge Voltage: automatically with temp. Sensor
Size (WxHxD): 46mm x 124mm x 127mm
Weight per Piece (excluding packing): 700g
Operat. Temperature Range: -40°C ... +70°C
Derating: 0,5W/°C at >+60°C
Mounting Method: Din-Rail
MTBF SN 29500 @ 40°C (h): 649.000h
Connection method: screw terminals
I2): 15A/360W resp. 30A/720W for up to 5s

Parámetros logísticos

ECCN:
País de origen:
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m