257778
VBA-4E2A1A-KE3-ZEL/E2L/SEL
AS-i Module with safe Output
The AS-Interface safety output module VBA-4E2A1A-KE3-ZEL/E2L/SEL is a switch cabinet module with a safe electronic output. The module has four inputs and two standard outputs. The inputs consist of three conventional inputs and one EDM input. The safety output module allows safe switching processes to take place remotely in the box. The parallel wiring of safe actuators in the box is a thing of the past. The housing is only 22.5 mm wide and takes up little space in the switch cabinet. A snap-on function mounts the module onto the 35 mm mounting strip in line with EN 50022. An addressing socket is integrated in the module. The connection is made via plug-in terminals. Four-way (black) terminal blocks are used for the inputs. The AS-Interface is connected via a two-way terminal block (yellow). This allows the sensors or the power supply to be easily separated for commissioning or service. Power is supplied to the inputs and connected sensors by an external auxiliary power supply. Yellow LEDs display the current switching status of the inputs and outputs. Red LEDs display communication errors and indicate that the A0 output bit is set. A green LED displays the operating voltage and the 0 address. Switching the programming plug accesses addressing for the safe output slave and the integrated A/B slave. Another A/B slave is available for diagnostics.
Slave type: | A/B slave, standard slave |
AS-Interface specification: | V3.0 |
Required master specification: | ≥ V2.1 |
Safety Integrity Level (SIL): | SIL 3 |
Performance level (PL): | PL e |
Mission Time (TM): | 20 a |
PFHd: | 1.91 E-9 |
PFD: | 5.94 E-7 |
LED FAULT: | error display; LED red red: communication error |
LED PWR: | AS-Interface voltage; LED green |
LED IN: | switching state (input); 4 LED yellow |
LED OUT: | For flashing patterns see diagnostics table |
Auxiliary voltage (input): | 24 V ± 20 % PELV |
Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
Rated operating current: | < 200 mA |
Protection class: | III |
Surge protection: | UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) |
Number/Type: | 3 standard inputs, 1 EDM input |
Supply: | from external auxiliary voltage UAUX |
Voltage: | 24 V DC |
Input current: | Static switching current: 4 mA at 24 V. Dynamic switching current: 15 mA at 24 V (T=100 μs) |
Sensor supply: | ≤ 100 mA |
Number/Type: | 2 output switch elements Max contact load: 0.5 A DC-13 at 30 V 1 safe electronic output |
Supply: | from external auxiliary voltage UAUX |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005/AC:2005 EN 61000-6-3:2007/A1:2011 |
Electromagnetic compatibility: | EN 61326-3-1:2008 |
Degree of protection: | EN 60529:2000 |
Electrical safety: | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
Emitted interference: | EN 61000-6-3:2007/A1:2011 |
AS-Interface: | EN 62026-2:2013 |
Noise immunity: | EN 61000-6-2:2005/AC:2005 EN 62026-2:2013 |
Functional safety: | IEC 61508:2010 (SIL3) EN 62061:2005 |
Profile: | Diagnostic slave: S-7.A.E, ID1 = 5 Input slave: S-7.A.E, ID1 = 7 |
IO code: | 7 |
ID code: | F |
Ambient temperature: | 0 ... 55 °C (32 ... 131 °F) |
Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection: | IP20 |
Connection: | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
Material: Housing: | PA 66-FR |
Mounting: | DIN mounting rail |
ECCN: | |
País de origen: | Türkei |
EAN: | 4050143042517 |
Peso: | 0,19 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |