KL6771
KL6771 | MP-Bus master terminal
The MP-Bus master terminal enables direct connection of MP-Bus slave devices. The MP-Bus was developed by Belimo for connecting valves, throttle valves, air valves and fire dampers for window ventilation systems. Up to sixteen field devices, eight drives and eight sensors can be connected to the KL6771. Process data exchange is fieldbus-independent. The Bus Terminal is configured and commissioned via TwinCAT function blocks. Status LEDs directly indicate the bus status. Several KL6771 terminals can be connected to the same Bus Coupler or Bus Terminal Controller.
Technology: | MP-Bus |
Number of channels: | 1 |
Data transfer standard: | MP-Bus |
Data transfer channels: | 1 |
MP-Bus devices: | max. 16 (8 drives/8 sensors) |
Data transfer rates: | 1200 baud |
Bus access: | polling |
Current consumption K-bus: | typ. 55 mA |
Current consumption power contacts: | typ. 10 mA + load |
Short-circuit proof: | yes |
Electrical isolation: | 500 V (K-bus/MP-Bus) |
Bit width in the process image: | input/output: 12 bytes |
Configuration: | TwinCAT (function blocks) |
Nominal voltage: | 24 V DC (-15 %/+20 %) |
Input voltage: | 24 V DC (-15 %/+20 %) |
Special features: | 8 drives/sensors; TwinCAT library: TwinCAT PLC MP-Bus |
Weight: | approx. 85 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals/markings: | CE, UL, ATEX |
Ex marking: | II 3 G Ex nA IIC T4 Gc |
ECCN: | |
País de origen: | |
EAN: | |
Peso: | 0,00 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |