Article image KL4132

Beckhoff KL4132

KL4132 | 2-channel analog output terminal -10…+10 V

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

The KL4132 analog output terminal generates signals in the range from -10 to +10 V. The voltage is supplied to the process level with a resolution of 16 bits and is electrically isolated. The output channels of a Bus Terminal have a common ground potential. The two run LEDs give an indication of the data exchange with the Bus Coupler.

Parámetros técnicos

Technology: single-ended
Number of outputs: 2
Power supply: via the K-bus
Signal voltage: -10…+10 V
Load: > 5 kΩ (short-circuit-proof)
Output error: < ±0.1 % (relative to end value)
Resolution: 16 bit
Conversion time: ~ 1.5 ms
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts: – (no power contacts)
Current consumption K-bus: typ. 75 mA
Bit width in the process image: output: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration: no address or configuration setting
Special features: increased resolution
Weight: approx. 85 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex

Parámetros logísticos

ECCN:
País de origen:
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m