KL4012
KL4012 | 2-channel analog output terminal 0…20 mA
The KL4012 analog output terminal generates analog output signals in the range from 0 to 20 mA. The power is supplied to the process level with a resolution of 12 bits and is electrically isolated. Ground potential for the output channels of the Bus Terminal is common with the 24 V DC supply. The output stages are powered by the 24 V supply. The run LEDs give an indication of the data exchange with the Bus Coupler.
Technology: | single-ended |
Number of outputs: | 2 |
Power supply: | 24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515) |
Signal current: | 0…20 mA |
Load: | < 500 Ω |
Output error: | < ±0.1 % (relative to end value) |
Resolution: | 12 bit |
Conversion time: | ~ 1.5 ms |
Electrical isolation: | 500 V (K-bus/signal voltage) |
Current consumption power contacts: | typ. 50 mA + load |
Current consumption K-bus: | typ. 60 mA |
Bit width in the process image: | output: 2 x 16 bit data (2 x 8 bit control/status optional) |
Configuration: | no address or configuration setting |
Weight: | approx. 80 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, UL, Ex, GL |
ECCN: | |
País de origen: | |
EAN: | |
Peso: | 0,00 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |