Article image KL2114

Beckhoff KL2114

KL2114 | 4-channel digital output terminal 24 V DC

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

The KL2114 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. The load current output of the KL2114 is protected against overload and short-circuit. The Bus Terminal contains four channels that indicate their signal state by means of light emitting diodes.

Parámetros técnicos

Connection technology: 2-/3-wire
Number of outputs: 4
Rated load voltage: 24 V DC (-15 %/+20 %)
Load type: ohmic, inductive, lamp load
Max. output current: 0.5 A (short-circuit-proof) per channel
Short circuit current: < 2 A
Breaking energy: < 150 mJ/channel
Reverse voltage protection:
Electrical isolation: 500 V (K-bus/field potential)
Current consumption power contacts: typ. 30 mA + load
Current consumption K-bus: typ. 9 mA
Bit width in the process image: 4 outputs
Configuration: no address or configuration setting
Weight: approx. 70 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex

Parámetros logísticos

ECCN:
País de origen:
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m