Article image ELX3202

Beckhoff ELX3202

ELX3202 | 2-channel analog input terminal RTD for 2, 3 and 4-wire connection, 16 bit, Ex i

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

The ELX3202 analog input terminal allows the direct connection of RTDs located in hazardous areas classified Zone 0/20 or 1/21. The circuitry of the ELX3202 can operate sensors with 2, 3 and 4-wire technology. Linearisation is carried out over the entire freely selectable temperature range. By default the terminal is set to PT100 sensors with 3-wire technology. The ELX3202 terminal indicates signal state and sensor malfunctions (e.g. wire breakage) by means of LEDs.

Parámetros técnicos

Number of inputs: 2 (differential)
Power supply: via the E-bus
Connection method: 2-, 3-, 4-wire (default: 2-wire)
Temperature range: -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors), for further types and details see documentation
Resolution: up to 0.01 °C per digit (preset: 0.1 °C per digit)
Measuring current: < 1 mA (depending on sensor and measuring range)
Measuring error: < ±0.3 % (relative to full scale value)
Internal resistance: typ. ≥ 10 kΩ (differential)
Input filter limit frequency: typ. 1 kHz
Sensor types: PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (10 Ω…4 kΩ), KT(Y) sensors
Conversion time: 10…3300 ms (adjustable, default: 170 ms)
Supply voltage electronics: 24 V DC (via power contacts), ELX9560 power supply
Current consumption power contacts: typ. 10 mA
Current consumption E-bus: typ. 70 mA
Special features: limit value monitoring, digital filter and characteristic curve linearisation integrated, connection method freely configurable
Weight: approx. 60 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/see documentation
Approvals/markings: CE, UL, ATEX, IECEx, cFMus
Ex marking: ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4

Parámetros logísticos

ECCN:
País de origen:
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m