ELX1052
ELX1052 | 2-channel digital input terminal NAMUR, Ex i
The ELX1052 digital input terminal allows the direct connection of intrinsically safe field devices located in hazardous areas classified Zone 0/20 or 1/21 and acquires their signals in compliance with IEC 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way wire breakage or short circuit can be detected in addition to the switching state. The LEDs represent the signal states or any error states.
Technology: | DC switching amplifier |
Specification: | IEC 60947-5-6 |
Number of inputs: | 2 |
Connection method: | 2-wire |
Open circuit voltage: | typ. 8.2 V DC |
“0” signal current: | ≤ 1.2 mA |
“1” signal current: | ≥ 2.1 mA |
Switching hysteresis: | typ. 0.3 mA |
Short-circuit current: | typ. 8.2 mA |
Fault detection: | I ≤ 200 µA (cable break), I ≥ 6.3 mA (short circuit) |
Max. switching frequency: | typ. 50 Hz (duty factor 50 %) |
Supply voltage electronics: | 24 V DC (via power contacts), ELX9560 power supply |
Current consumption power contacts: | typ. 10 mA + load |
Current consumption E-bus: | typ. 50 mA |
Weight: | approx. 55 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/see documentation |
Approvals/markings: | CE, UL, ATEX, IECEx, cFMus |
Ex-Marking: | ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4 |
ECCN: | |
País de origen: | |
EAN: | |
Peso: | 0,00 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |