The EJ3214 analog input allows four resistance sensors to be connected directly. The EtherCAT plug-in module's circuit can operate sensors using the 2- or 3-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The EJ3214’s standard settings are: resolution 0.1 °C. Sensor malfunctions such as broken wires are indicated by error LEDs.
Connection method: | 2- or 3-wire (default: 3-wire) |
Sensor types: | PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation) |
Number of inputs: | 4 |
Measuring range: | -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors) |
Resolution: | 0.1 °C per digit |
Measuring error: | < ±0.5 °C for PT sensors, 4 x 3-wire connection |
Input filter limit frequency: | typ. 1 kHz |
Conversion time: | approx. 170 ms default setting |
Distributed clocks: | – |
Current consumption E-bus: | typ. 160 mA |
Electrical isolation: | 500 V (E-bus/field potential) |
Special features: | integrated digital filter, limit value monitoring, variable connection technology |
Dimensions (W x H x D): | approx. 12 mm x 66 mm x 55 mm |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Approvals/markings: | CE, UL |