Phoenix Contact 2908743

FA MCR-EX-HT-TS-I-OLP-PT

DIN rail adapter for head-mounted transducers. Suitable for 35 mm DIN rails in accordance with EN 60715. Programming adapter with USB and T port interface, 2.4 m for programming FA MCR-..., MCR-...-LP-..., and MCR-...-HT-.. modules. Display unit for plugging directly into the FA MCR-.. head transmitter. Field housing for the installation of head transmitters with or without display unit. For direct connection to the process. Wall fastening for FA MCR-HT-FH field housing. Pipe fastening for FA MCR-HT-FH field housing. The output loop-powered head transmitter transmits up to two sensor signals from RTD and TC sensors as well as from resistance-type sensors and voltage sensors via HART communication or 4 .. 20 mA, configurable. SIL 2/3, intrinsic safety. USB HART modem cable for communication between a PC and HART devices, cable length: 1m.

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Technical parameters

Umgebungstemperatur (Betrieb): -40 °C ... 85 °C
Umgebungstemperatur (Lagerung/Transport): -50 °C ... 100 °C
Max. Einsatzhöhe: ≤ 4000 m (über NN)
Zulässige Luftfeuchtigkeit (Betrieb): 5 % ... 95 % (Betauung zulässig)
Schutzart: IP33 (bei Einbau im Feldgehäuse IP66/67, NEMA 4X)
Verwendbare Sensortypen (RTD): Pt-, Ni-, Cu-Sensoren: 2-, 3-, 4 Leiter
Verwendbare Sensortypen (TC): A, B, C, D, E, J, K, L, N, R, S, T, U
Widerstandsbereich linear: 10 Ω ... 2000 Ω (Mindestmessspanne: 10 Ω)
Ausgangssignal Strom: 4 mA ... 20 mA (HART)
max. Ausgangsstrom: 23 mA
Versorgungsspannungsbereich: 11 V ... 42 V (Standard)
Anschlussart: Push-in-Anschluss
Abisolierlänge: 10 mm
Leiterquerschnitt starr: 0,2 mm² ... 1,5 mm²
Leiterquerschnitt flexibel: 0,2 mm² ... 1,5 mm²
Leiterquerschnitt AWG: 24 ... 16
Überspannungskategorie: II
Verschmutzungsgrad: 2
Montagehinweis: Einbau im Anschlusskopf nach DIN 43729 Form B
Konformität: CE-konform
ATEX:  II 1G Ex ia IIC T6...T4 Ga
IECEx: Ex ia IIC T6...T4 Ga
UL, USA / Kanada: UL 61010 Recognized
FM: NI / Class I / Div. 1, 2 / Group ABCD T6/T5/T4
CSA: Exia / Class I / Group ABCD T6/T5/T4
China RoHS: Zeitraum für bestimmungsgemäße Verwendung: unbegrenzt = EFUP-e
eCl@ss 10.0.1: 27210129
eCl@ss 4.0: 27200206
eCl@ss 4.1: 27200206
eCl@ss 5.0: 27200206
eCl@ss 5.1: 27200206
eCl@ss 6.0: 27200206
eCl@ss 7.0: 27200206
eCl@ss 8.0: 27200206
eCl@ss 9.0: 27210129
ETIM 2.0: EC001426
ETIM 3.0: EC001426
ETIM 4.0: EC001426
ETIM 5.0: EC001446
ETIM 6.0: EC002919
ETIM 7.0: EC002919

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m