Phoenix Contact 2906367

TRIO-UPS-2G/3AC/24DC/20

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Technical parameters

Width: 88 mm
Height: 130 mm
Depth: 160 mm
Width with alternative assembly: 160 mm
Height with alternative assembly: 130 mm
Depth with alternative assembly: 88 mm
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
Degree of protection: IP20
Inflammability class in acc. with UL 94 (housing / terminal blocks): V0
Ambient temperature (operation): -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested): -40 °C
Ambient temperature (storage/transport): -40 °C ... 85 °C
Max. permissible relative humidity (operation): ≤ 95 % (At +25°C, non-condensing)
Climatic class: 3K3 (in acc. with EN 60721)
Degree of pollution: 2
Installation height: ≤ 4000 m (> 2000 m, observe derating)
Inrush current limiting/I²t: < 0.76 A2s
Mains buffering time: ≥ 25 ms (400 V AC)
Typical response time: 200 ms
Input fuse, integrated: 6.3 A (slow-blow, internal)
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (> 24 V constant capacity)
Nominal output current (IN): 20 A
Dynamic Boost (IDyn.Boost): 30 A
Derating: > 60 °C (2.5%/K of POut nom.)
Control deviation: < 0.3 % (Static load change 10 % ... 90 %)
Maximum power dissipation in no-load condition: < 3.6 W (400 V AC)
Efficiency: typ. 93 % (400 V AC)
Residual ripple: < 20 mV
Connection in parallel: yes, with diode module uncoupled
Surge protection against internal surge voltages: < 30 V DC
Feedback voltage resistance: ≤ 35 V DC
Net weight: 1.71 kg
Insulation voltage input/output: 4 kV AC (type test)
Protection class: I
MTBF (IEC 61709, SN 29500): > 1108720 h (400 V AC, at 25°C)
Mounting position: horizontal DIN rail NS 35, EN 60715
Assembly instructions: alignable: horizontally 0 mm, vertically 50 mm
Connection method: Push-in connection
Conductor cross section solid min.: 0.2 mm²
Conductor cross section solid max.: 4 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 10 mm
Connection method: Push-in connection
Conductor cross section solid min.: 0.2 mm²
Conductor cross section solid max.: 10 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 6 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 8
Stripping length: 15 mm
Connection method: Push-in connection
Conductor cross section solid min.: 0.2 mm²
Conductor cross section solid max.: 1.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
Charge characteristic curve: IU0U
Charge current: 0.5 A ... 3 A (-25 °C ... 60 °C)
EMC requirements for noise immunity: EN 61000-6-1
EMC requirements for noise emission: EN 61000-6-3
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard – Safety extra-low voltage: IEC 61010 (SELV) / (PELV)
Standard - Safe isolation: DIN VDE 0100-410
Standard - power supply devices for low voltage with DC output: EN 61204-3
UL approvals: UL Listed UL 61010
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Conducted noise emission: EN 61000-6-3 (Class B)
Noise emission: EN 61000-6-3 (Class B)
DNV GL conducted interference: Class B
Additional text: Area power distribution
DNV GL noise radiation: Class B
Additional text: Bridge and deck area
Electrostatic discharge: EN 61000-4-2
Contact discharge: 6 kV (Test Level 4)
Discharge in air: 8 kV (Test Level 4)
Electromagnetic HF field: EN 61000-4-3
Frequency range: 80 MHz ... 6 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst): EN 61000-4-4
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Input: 2 kV (Test Level 3 - symmetrical)
Output: 1 kV (Test Level 1 - symmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference: EN 61000-4-6
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Voltage: 10 V (Test Level 3)
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave): EN 61000-4-12
Input: 2 kV (symmetrical)
Comments: Criterion A
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
REACh SVHC: Lead 7439-92-1
eCl@ss 10.0.1: 27040705
eCl@ss 9.0: 27040705
ETIM 6.0: EC000382
ETIM 7.0: EC000382

Logistic parameters

ECCN:
Country of Origin: CN
EAN:
Weight: 2.007 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m