258421
VBA-4E-G12-ZEJ
AS-Interface sensor module
The VBA-4E-G12-Z*J is an AS-Interface trigger module with 4 inputs. 2- and 3-wire sensors as well as mechanical contacts can be connected to the plus switching electronic inputs. G12 flat module. 4 inputs (PNP)fa. The solid housing permits fast mounting without tools as well as easy removal without tools. The stainless steel shell and the cast housing ensure durability and a high protection category. The connection to the AS-Interface cable is achieved via penetration technology in the integrated flat cable. The insert for the flat cables can be turned in two orientations. All connections to inputs are implemented via metal inserts for high stability. The connection to the sensors is achieved via a M12 x 1 circular connector with SPEEDCON quick locking option. The inputs and the connected sensors are supplied via the internal power supply of the module (from AS-Interface). To indicate the current switching state there is an LED for each channel fitted to the top of the module. An LED to indicate the AS-Interface voltage and that the module has an address of 0 is available, another indicates errors in the AS-Interface communication as well as periphery faults. This module can be mounted in any position using three screws or can be snapped onto the DIN rail using the stainless steel holder.
Slave type: | A/B slave |
AS-Interface specification: | V3.0 |
Required master specification: | ≥ V2.1 |
UL File Number: | E223772 |
MTTFd: | 410 a |
Mission Time (TM): | 20 a |
Diagnostic Coverage (DC): | 0 % |
LED FAULT: | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply |
LED PWR: | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
LED IN: | switching state (input); 4 LED yellow |
Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
Rated operating current: | ≤ 40 mA (without sensors) / max. 240 mA |
Protection class: | III |
Surge protection: | Ue: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
Number/Type: | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Supply: | from AS-Interface |
Voltage: | 21 ... 31 V |
Current loading capacity: | ≤ 200 mA, overload and short-circuit protected |
Input current: | ≤ 8 mA (limited internally) |
Switching point: | according to DIN EN 61131-2 (Type 2) |
: 0 (unattenuated): | ≤ 2 mA |
: 1 (attenuated): | ≥ 6 mA |
Signal delay: | < 1 ms (input/AS-Interface) |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
Degree of protection: | EN 60529:2000 |
Fieldbus standard: | EN 62026-2:2013 |
Input: | EN 61131-2 |
Emitted interference: | EN 61000-6-4:2007 |
AS-Interface: | EN 62026-2:2013 |
Noise immunity: | EN 61000-6-2:2005 EN 62026-2:2013 |
Profile: | S-0.A.0 |
IO code: | 0 |
ID code: | A |
ID1 code: | 7 |
ID2 code: | 0 |
Data bits (function via AS-Interface): | input output |
Electromagnetic compatibility: D0: | IN1 - |
Electromagnetic compatibility: D1: | IN2 - |
Electromagnetic compatibility: D2: | IN3 - |
Electromagnetic compatibility: D3: | IN4 - |
Parameter bits (programmable via AS-i): | function |
Electromagnetic compatibility: P0: | not used |
Electromagnetic compatibility: P1: | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
Electromagnetic compatibility: P2: | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
Electromagnetic compatibility: P3: | not used |
Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity: | 85 % , noncondensing |
Climatic conditions: | For indoor use only |
Altitude: | ≤ 2000 m above MSL |
Shock and impact resistance: | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
Vibration resistance: | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Pollution degree: | 3 |
Degree of protection: | IP67 |
Connection: | cable piercing method flat cable yellow inputs: M12 round connector |
Material: Housing: | PBT |
Mass: | 200 g |
Tightening torque, cable gland: | 0.4 Nm |
Mounting: | Mounting plate |
ECCN: | |
Country of Origin: | Indonesien |
EAN: | 4050143042760 |
Weight: | 0.23 kg |
Length: | 0.00 m |
Width: | 0.00 m |