Pepperl+Fuchs 257778

VBA-4E2A1A-KE3-ZEL/E2L/SEL

AS-i Module with safe Output

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The AS-Interface safety output module VBA-4E2A1A-KE3-ZEL/E2L/SEL is a switch cabinet module with a safe electronic output. The module has four inputs and two standard outputs. The inputs consist of three conventional inputs and one EDM input. The safety output module allows safe switching processes to take place remotely in the box. The parallel wiring of safe actuators in the box is a thing of the past. The housing is only 22.5 mm wide and takes up little space in the switch cabinet. A snap-on function mounts the module onto the 35 mm mounting strip in line with EN 50022. An addressing socket is integrated in the module. The connection is made via plug-in terminals. Four-way (black) terminal blocks are used for the inputs. The AS-Interface is connected via a two-way terminal block (yellow). This allows the sensors or the power supply to be easily separated for commissioning or service. Power is supplied to the inputs and connected sensors by an external auxiliary power supply. Yellow LEDs display the current switching status of the inputs and outputs. Red LEDs display communication errors and indicate that the A0 output bit is set. A green LED displays the operating voltage and the 0 address. Switching the programming plug accesses addressing for the safe output slave and the integrated A/B slave. Another A/B slave is available for diagnostics.

Technical parameters

Slave type: A/B slave, standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
Safety Integrity Level (SIL): SIL 3
Performance level (PL): PL e
Mission Time (TM): 20 a
PFHd: 1.91 E-9
PFD: 5.94 E-7
LED FAULT: error display; LED red red: communication error
LED PWR: AS-Interface voltage; LED green
LED IN: switching state (input); 4 LED yellow
LED OUT: For flashing patterns see diagnostics table
Auxiliary voltage (input): 24 V ± 20 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: < 200 mA
Protection class: III
Surge protection: UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 3 standard inputs, 1 EDM input
Supply: from external auxiliary voltage UAUX
Voltage: 24 V DC
Input current: Static switching current: 4 mA at 24 V. Dynamic switching current: 15 mA at 24 V (T=100 μs)
Sensor supply: ≤ 100 mA
Number/Type: 2 output switch elements Max contact load: 0.5 A DC-13 at 30 V 1 safe electronic output
Supply: from external auxiliary voltage UAUX
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005/AC:2005 EN 61000-6-3:2007/A1:2011
Electromagnetic compatibility: EN 61326-3-1:2008
Degree of protection: EN 60529:2000
Electrical safety: EN ISO 13849-1:2008 EN ISO 13849-2:2012
Emitted interference: EN 61000-6-3:2007/A1:2011
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005/AC:2005 EN 62026-2:2013
Functional safety: IEC 61508:2010 (SIL3) EN 62061:2005
Profile: Diagnostic slave: S-7.A.E, ID1 = 5 Input slave: S-7.A.E, ID1 = 7
IO code: 7
ID code: F
Ambient temperature: 0 ... 55 °C (32 ... 131 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Degree of protection: IP20
Connection: removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mounting: DIN mounting rail

Logistic parameters

ECCN:
Country of Origin: Türkei
EAN: 4050143042517
Weight: 0.19 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m