213837
NBN40-U2K-N0 123G1xxD
Inductive sensor
Series: VariKont ®, Housing material: PA, Output type: 2-wire, Installation: non-flush, Type of voltage: DC, Connection type: screw terminals, Degree of protection: IP68 / IP69Kfa
Switching function: | Normally closed (NC) |
Output type: | NAMUR |
Rated operating distance: | 40 mm |
Installation: | non-flush |
Assured operating distance: | 0 ... 32.4 mm |
Actual operating distance: | 36 ... 44 mm |
Reduction factor rAl: | 0.31 |
Reduction factor rCu: | 0.3 |
Reduction factor r304: | 0.74 |
Output type: | 2-wire |
Nominal voltage: | 8 V |
Switching frequency: | 0 ... 150 Hz |
Hysteresis: | typ. 5 % |
Reverse polarity protection: | yes |
Short-circuit protection: | yes |
Current consumption: Measuring plate not detected: | min. 2.2 mA |
Current consumption: Measuring plate detected: | ≤ 1 mA |
Switching state indicator: | LED, yellow |
MTTFd: | 1415 a |
Mission Time (TM): | 20 a |
Diagnostic Coverage (DC): | 0 % |
Standard conformity: NAMUR: | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
Standard conformity: Electromagnetic compatibility: | NE 21:2007 |
Standard conformity: Standards: | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
UL approval: Ordinary Location: | E87056 |
UL approval: Hazardous Location: | E501628 |
UL approval: Control drawing: | 116-0451 |
CCC approval: | CCC approval / marking not required for products rated ≤36 V |
Ambient temperature: | -25 ... 100 °C (-13 ... 212 °F) |
Storage temperature: | -40 ... 100 °C (-40 ... 212 °F) |
Connection type: | screw terminals |
Information for connection: | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
Core cross-section: | up to 2.5 mm2 |
UL approval: Minimum core cross-section: | without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
UL approval: Maximum core cross-section: | without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
Housing material: | PA |
Sensing face: | PA |
Degree of protection: | IP68 / IP69K |
Mass: | 225 g |
Note: | Tightening torque: 1.8 Nm (housing) |
Use in the hazardous area: | see instruction manuals |
ECCN: | |
Country of Origin: | Indonesien |
EAN: | 4050143027538 |
Weight: | 0.22 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |