Pepperl+Fuchs 095288

SC2-N0-GN

Inductive slot sensor

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Series: Slot type, Housing material: PBT, Output type: 2-wire, Type of voltage: DC, Connection type: cable PVC , 500 mm, Degree of protection: IP67fa

Technical parameters

Switching function: Normally closed (NC)
Output type: NAMUR
Slot width: 2 mm
Depth of immersion (lateral): 5 ... 7 mm , typ. 6 mm
Output type: 2-wire
Nominal voltage: 8.2 V (Ri approx. 1 kΩ)
Operating voltage: 5 ... 25 V
Switching frequency: 0 ... 5000 Hz
Hysteresis: 0.11 ... 0.2 mm
Current consumption: Measuring plate not detected: ≥ 3 mA
Current consumption: Measuring plate detected: ≤ 1 mA
Switching state indicator: LED, yellow
MTTFd: 5790 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
Standard conformity: NAMUR: EN 60947-5-6:2000 IEC 60947-5-6:1999
Standard conformity: Electromagnetic compatibility: NE 21:2007
Standard conformity: Standards: EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
IECEx approval: Equipment protection level Ga: IECEx PTB 11.0091X
IECEx approval: Equipment protection level Gb: IECEx PTB 11.0091X
IECEx approval: Equipment protection level Da: IECEx PTB 11.0091X
IECEx approval: Equipment protection level Mb: IECEx PTB 11.0091X
ATEX approval: Equipment protection level Ga: PTB 99 ATEX 2219 X
ATEX approval: Equipment protection level Gb: PTB 99 ATEX 2219 X
ATEX approval: Equipment protection level Gc: PF13CERT2895 X
ATEX approval: Equipment protection level Da: PTB 99 ATEX 2219 X
UL approval: cULus Listed, General Purpose
ATEX approval: Ordinary Location: E87056
ATEX approval: Hazardous Location: E501628
ATEX approval: Control drawing: 116-0453
CSA approval: cCSAus Listed, General Purpose
CCC approval: CCC approval / marking not required for products rated ≤36 V
Ambient temperature: -25 ... 100 °C (-13 ... 212 °F)
Connection type: cable PVC , 500 mm
Core cross-section: 0.06 mm2
Housing material: PBT
Degree of protection: IP67
Use in the hazardous area: see instruction manuals

Logistic parameters

ECCN:
Country of Origin: ID
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m