Ifm SM6500

Magnetic-inductive flow meter. SMK12GGXFRKG/US-100

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Technical parameters

Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Process connection: threaded connection Rc 1/2 internal thread DN15
Measuring range [°C]: -20...80
Special feature: Gold-plated contacts
Application: totaliser function; for industrial applications
Media: conductive liquids; water; hydrous media
Note on media: conductivity: ≥ 20 µS/cm viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C]: -10...70
Pressure rating [bar]: 16
Pressure rating [Mpa]: 1.6
Operating voltage [V]: 18...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]: 95; (24 V)
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: 5
Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Inputs: counter reset
Total number of outputs: 2
Output signal: switching signal; analogue signal; pulse signal; IO-Link; (configurable)
Electrical design: PNP/NPN
Number of digital outputs: 2
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 200
Number of analogue outputs: 1
Analogue current output [mA]: 4...20; (scalable)
Max. load [Ω]: 500
Analogue voltage output [V]: 0...10; (scalable)
Min. load resistance [Ω]: 2000
Pulse output: flow rate meter
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Overload protection: yes
Measuring range: 0.1...25 l/min 0.005...1.5 m³/h
0.1...25 l/min: 0.005...1.5 m³/h
Display range: -30...30 l/min -1.8...1.8 m³/h
-30...30 l/min: -1.8...1.8 m³/h
Resolution: 0.02 l/min 0.002 m³/h
0.02 l/min: 0.002 m³/h
Set point SP: 0.25...25 l/min 0.015...1.5 m³/h
0.25...25 l/min: 0.015...1.5 m³/h
Reset point rP: 0.1...24.9 l/min 0.005...1.495 m³/h
0.1...24.9 l/min: 0.005...1.495 m³/h
Analogue start point ASP: 0...20 l/min 0...1.2 m³/h
0...20 l/min: 0...1.2 m³/h
Analogue end point AEP: 5...25 l/min 0.3...1.5 m³/h
5...25 l/min: 0.3...1.5 m³/h
In steps of: 0.02 l/min 0.002 m³/h
0.02 l/min: 0.002 m³/h
Pulse value: 0.00001...30 000 m³
Pulse length [s]: 0,01...2
Measuring range [°C]: -20...80
Resolution [°C]: 0.2
Set point SP [°C]: -19.2...80
Reset point rP [°C]: -19.6...79.6
Analogue start point [°C]: -20...60
Analogue end point [°C]: 0...80
In steps of [°C]: 0.2
Accuracy (in the measuring range): ± (0,8 % MW + 0,5 % MEW)
Repeatability: ± 0,2% MEW
Accuracy [K]: ± 2,5 (Q > 1 l/min)
Response time [s]: 0.15; (dAP = 0, T19)
Delay time programmable dS, dr [s]: 0...50
Damping for the switching output dAP [s]: 0...5
Dynamic response T05 / T09 [s]: T09 = 20 (Q > 1 l/min)
Parameter setting options: Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/pulse output; start-up delay; display can be deactivated; Display unit
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.1
SDCI standard: IEC 61131-9
IO-Link device ID: 569 / 00 02 39 h
Profiles: Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode: yes
Required master port type: A
Process data analogue: 3
Process data binary: 2
Min. process cycle time [ms]: 5
Ambient temperature [°C]: -10...60
Storage temperature [°C]: -25...80
Protection: IP 67
EMC: DIN EN 60947-5-9
Shock resistance: DIN IEC 68-2-27 20 g (11 ms)
DIN IEC 68-2-27: 20 g (11 ms)
Vibration resistance: DIN IEC 68-2-6 5 g (10...2000 Hz)
DIN IEC 68-2-6: 5 g (10...2000 Hz)
MTTF [years]: 145
UL approval: UL Approval no. I010
UL Approval no.: I010
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 580.5
Materials: stainless steel (1.4404 / 316L); PBT-GF20; PC; FKM; TPE
Materials (wetted parts): stainless steel (1.4404 / 316L); PEEK; EPDM
Process connection: threaded connection Rc 1/2 internal thread DN15
Display: Display unit 6 x LED, green (l/min, m³/h, l, m³, 10³, °C) switching status 2 x LED, yellow measured values alphanumeric display, 4-digit programming alphanumeric display, 4-digit
Display unit: 6 x LED, green (l/min, m³/h, l, m³, 10³, °C)
switching status: 2 x LED, yellow
measured values: alphanumeric display, 4-digit
programming: alphanumeric display, 4-digit
Remarks: MW = measured value MEW = Final value of the measuring range
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.58 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m