Ifm LR8320

Continuous level sensor (guided wave radar). LR0000--BN34ASPKG/US

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

For the reliable level control in tanks and containers. Suitable for water and water-based media. Modular system consisting of evaluation unit and probe. Adaptation to different container heights through shortening of the probe

Technical parameters

Number of inputs and outputs: Number of digital outputs: 4
Probe length L [mm]: 100...2000
Process connection: 3/4" NPT
Special feature: Gold-plated contacts
Media: Liquids
Dielectric constant of the medium: > 5
Recommended media: water; hydrous media
Medium temperature [°C]: -25...80; (90: < 1 h)
Tank pressure [bar]: -1...16
Operating voltage [V]: 18...30 DC
Current consumption [mA]: < 25
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: < 3
Number of inputs and outputs: Number of digital outputs: 4
Total number of outputs: 4
Output signal: switching signal; IO-Link
Electrical design: PNP/NPN
Number of digital outputs: 4
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2.5
Permanent current rating of switching output DC [mA]: 200
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Overload protection: yes
Probe length L [mm]: 100...2000
Active range A [mm]: L-40
Inactive range I1 / I2 [mm]: 30 / 10
Sampling rate [Hz]: 4
Set point SP [mm]: ≥ 15...L-30
Reset point rP [mm]: ≥ 10...L-35
In steps of [mm]: 5
Hysteresis [mm]: > 5
Repeatability [mm]: 5
Measuring error [mm]: ± 7
Offset error [mm]: 5
Resolution [mm]: 1
Temperature drift per 10 K: ± 0.2 %
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.1
SDCI standard: IEC 61131-9
IO-Link device ID: 979 d / 00 03 D3 h
Profiles: Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode: yes
Required master port type: A
Process data analogue: 3
Process data binary: 4
Min. process cycle time [ms]: 3.2
Ambient temperature [°C]: -25...60
Storage temperature [°C]: -40...85
Protection: IP 68; IP 69K; (7 days / 1 m water depth / 0.1 bar: IP 68)
EMC: DIN EN 61000-6-2 DIN EN 61000-6-3 : in a closed metal tank DIN EN 61000-6-4 : in plastic or open metal tanks
DIN EN 61000-6-3: : in a closed metal tank
DIN EN 61000-6-4: : in plastic or open metal tanks
Shock resistance: DIN EN 60068-2-27 50 g (11 ms) / 25 g (6 ms) with reference rod 0.5 m
DIN EN 60068-2-27: 50 g (11 ms) / 25 g (6 ms) with reference rod 0.5 m
Vibration resistance: DIN EN 60068-2-6 5 g (10...2000 Hz) / 1 g (5...200 Hz) with reference rod 0.5 m
DIN EN 60068-2-6: 5 g (10...2000 Hz) / 1 g (5...200 Hz) with reference rod 0.5 m
MTTF [years]: 242
UL approval: UL Approval no. H011 File number UL E174191
UL Approval no.: H011
File number UL: E174191
Weight [g]: 444.8
Materials: stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; PEI
Materials (wetted parts): stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM
Process connection: 3/4" NPT
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.44 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m