Ifm AC2489

AS-Interface CompactLine module. CompactM8 2 x 4 DI A/B

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Mechanical end stop to protect the O-ring from destruction

Technical parameters

Operating voltage [V]: 26.5...31.6 DC; ("supply class 2" to cULus)
Max. current consumption from AS-i [mA]: 250
Number of inputs and outputs: Number of digital inputs: 8
Number of digital inputs: 8; (2 x Slave)
Input circuit of digital inputs: PNP; (type 2 according to IEC 61131-2)
Sensor supply of the inputs: AS-i
Voltage supply [V]: 18...30
Max. total current rating of inputs [mA]: 180
Min. switching level high signal [V]: 11
Digital inputs protected against short circuits: yes
Ambient temperature [°C]: -25...60
Max. relative air humidity [%]: 90; (non condensing)
Max. height above sea level [m]: 2000
Protection: IP 65; IP 67; IP 68
EMC: EN 62026-2 EN 61000-6-2 EN 61000-6-3
AS-i version: 3.0
Extended addressing mode possible: yes
AS-i profile: S-0.A.E
AS-i I/O configuration [hex]: 0
AS-i ID code [hex]: A.E
AS-i certificate: 133901
Assignment of the data bits: data bit D0 D1 D2 D3 input 1 2 3 4 socket I-1 I-2 I-3 I-4 pin 4 4 4 4
data bit: D0
input: 1
socket: I-1
pin: 4
Assignment of the parameter bits: parameter bit Designation P0 not used P1 peripheral fault indication : 1 activated / 0 deactivated P2 not used P3 not used
parameter bit: Designation
P0: not used
P1: peripheral fault indication
P2: not used
P3: not used
Weight [g]: 152
Type of mounting: backplane mounting
Materials: PBT
Display: switching status LED, yellow operation LED, green errors LED, red
switching status: LED, yellow
operation: LED, green
errors: LED, red
Accessories (supplied): Label tags Protective caps: 2
Accessories (optional): Protective cap: M8, E73005 Flat cable insulation displacement connector: 1 m, round cable, E70583 Flat cable insulation displacement connector: M12, E70096 DIN rail adapter:, E73007
Remarks: Do not connect any of the following points to an external potential: I-, I+, I1, I2, I3, I4 The connections are electrically connected with the AS-i cable. default setting of the ID1 codes: slave 1=1 / slave 2=2
Pack quantity: 1 pcs.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.15 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m