Article image KL6001

Beckhoff KL6001

KL6001 | Serial interface RS232

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL6001 serial interface allows devices with an RS232 interface to be connected. The interface operates in conformity with the CCITT V.28/DIN 66 259-1 standards. The device connected to the terminal communicates with the automation device via the Bus Coupler. The active communication channel operates independently of the higher-level bus system in full duplex mode at up to 19,200 baud. The RS232 interface guarantees high immunity to interference through electrically isolated signals.

Technical parameters

Technology: RS232
Data transfer channels: 2 (1/1), TxD and RxD, full duplex
Data transfer rates: 1200…19,200 baud; default: 9600 baud, 8 data bits, no parity and one stop bit
Bit distortion: < 3 %
Line impedance:
Cable length: max. 15 m
“0“ signal voltage: -18…-3 V
“1“ signal voltage: 3…18 V
Power supply: via the K-bus
Current consumption K-bus: typ. 55 mA
Current consumption power contacts: – (no power contacts)
Electrical isolation: 500 V (K-bus/signal voltage)
Data buffer: 128 bytes receive buffer, 16 bytes transmit buffer
Bit width in the process image: input/output: 3 x 8 bit user data, 1 x 8 bit control/status (up to 5 x 8 bit user data are possible)
Configuration: no address setting, configuration via Bus Coupler or controller
Special features: high interference immunity, electrically isolated signals
Weight: approx. 80 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m