KL5001
KL5001 | SSI encoder interface
The KL5001 SSI interface terminal enables the direct connection of an SSI encoder that is powered via the SSI interface. The interface circuit generates a pulse for reading the encoder and makes the incoming data stream available to the controller as a data word in the process image. Various operating modes, transmission frequencies and bit widths can be permanently stored in a control register. A screen can be connected via the KL9195 shield terminal.
Technology: | SSI encoder interface |
Number of channels: | 1 encoder interface |
Encoder connection: | binary input: D+, D-, binary output: Cl+, Cl- |
Power supply: | 24 V DC via power contacts |
Current consumption: | typ. 20 mA without encoder |
Current consumption power contacts: | typ. 20 mA + load |
Encoder supply: | 24 V DC via power contacts |
Data transfer rates: | variable up to 1 MHz, 250 kHz default |
Serial input: | 24 bit width (variable) |
Data direction: | read |
Signal output: | difference signal (RS422) |
Signal input: | difference signal (RS422) |
Electrical isolation: | 500 V (K-bus/field potential) |
Current consumption K-bus: | typ. 25 mA |
Bit width in the process image: | input: 1 x 32 bit data (1 x 8 bit control/status optional) |
Weight: | approx. 60 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, UL, Ex |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |