KL2722 | 2-channel triac output terminal 12…230 V AC
The KL2722 output terminal uses a power switch to control mains voltage from 12 to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The KL2722 has two mutually locked outputs.
Connection technology: | 4-wire |
Number of outputs: | 2 x make contacts, mutually locked |
Nominal voltage: | 12…230 V AC |
Load type: | ohmic, inductive |
Max. output current: | 1 A (leakage current: typ. 0.8 mA, max. 1.5 mA) per channel |
Frequency range: | 47…63 Hz |
Surge voltage protection: | > 275 V AC |
Peak current: | 40 A (16 ms), 3 A (30 s) |
Switch-on time: | 0.1…10 ms, zero crossing |
Switch-off time: | T/2 |
Max. residual voltage: | 1.5 V |
Electrical isolation: | 500 V (K-bus/field voltage), 3750 V AC (1 min.) |
Leakage current (OFF state): | typ. 0.8 mA, max. 1.5 mA |
Current consumption power contacts: | only leakage and load current |
Current consumption K-bus: | typ. 10 mA |
Bit width in the process image: | 2 outputs |
Configuration: | no address or configuration setting |
Special features: | reverse motors (blinds) |
Weight: | approx. 55 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, Ex, GL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |