KL1312
KL1312 | 2-channel digital input terminal 24 V DC for type 2 sensors
The KL1312 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes. The input signal corresponds to the standard EN 61131-2, type 2. This way, it is possible to connect 2-wire sensors.
Connection technology: | 4-wire |
Specification: | EN 61131-2, type 2 |
Number of inputs: | 2 |
Nominal voltage: | 24 V DC (-15 %/+20 %) |
“0” signal voltage: | -3…+5 V (EN 61131-2, type 2) |
“1” signal voltage: | 11…30 V (EN 61131-2, type 2) |
Input filter: | typ. 0.2 ms |
Input current: | typ. 6 mA (EN 61131-2, type 2) |
Current consumption K-bus: | typ. 3 mA |
Electrical isolation: | 500 V (K-bus/field potential) |
Bit width in the process image: | 2 inputs |
Configuration: | no address or configuration setting |
Weight: | approx. 50 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals/markings: | CE, UL, ATEX |
Ex marking: | II 3 G Ex nA IIC T4 Gc |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |