Article image EQ3314-0002

Beckhoff EQ3314-0002

EQ3314-0002 | 4-channel analog input thermocouple

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EQ3314 EtherCAT Box with analog inputs permits four thermocouples to be directly connected. The module’s circuit can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through a temperature measurement in the connecting plugs. This means that standard extension leads can be connected. The EP3314 can also be used for mV measurement.

Technical parameters

Number of inputs: 4
Housing width: 39 mm
Connection method: screw type M12, 2-wire connection for thermocouple
Protocol: EtherCAT
Bus interface: 2 x M8 socket, shielded, screw type
Sensor types: types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Signal type: thermocouple
Measuring range: depending on sensor type; preset value is type K, -100…+1370 °C
Resolution: 0.1 °C per digit
Measuring error: < ±0.3 % for type K (relative to full scale value; further types see documentation)
Conversion time: 2.5 s up to 20 ms, see documentation, default: approx. 250 ms
Distributed clocks:
Input filter: 5 variations, configurable
Current consumption from US: 120 mA
Power supply connection: feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image: 4 x 32 bit TC input, 4 x 16 bit TC output
Electrical isolation: 500 V
Special features: stainless steel, Hygienic Design
Dimensions (W x H x D): 39 mm x 160 mm x 43 mm
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 69K (according to EN 60529)/variable
Approvals/markings: CE, UL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m