EQ2008-0002
EQ2008-0002 | 8-channel digital output 24 V DC
The EQ2008 EtherCAT Box with digital outputs connects binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 0.5 A and indicate their status through light emitting diodes. The signals are connected via M12 screw type connectors. The outputs are short-circuit-proof and protected against inverse connection.
Number of outputs: | 8 |
Rated load voltage: | 24 V DC (-15 %/+20 %) |
Output connections: | M12, screw type |
Protocol: | EtherCAT |
Bus interface: | 2 x M8 socket, shielded, screw type |
Load type: | ohmic, inductive, lamp load |
Nominal output voltage: | 24 V DC (-15 %/+20 %) |
Max. output current: | 0.5 A per channel, individually short-circuit-proof, total current max. 4 A |
Short circuit current: | typ. 1.5 A |
Distributed clocks: | – |
Auxiliary power current: | typ. 20 mA + load |
Current consumption from US (without sensor current): | 120 mA |
Power supply connection: | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Bit width in the process image: | 8 outputs |
Electrical isolation: | 500 V |
Special features: | V2A stainless steel, Hygienic Design |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 69K (according to EN 60529)/variable |
Approvals: | CE, UL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |