ELX3351-0090 | 1-channel analog input terminal strain gauge, 16 bit, Ex i, TwinSAFE SC
The analog ELX3351-0090 input terminal enables direct connection of a resistor bridge or load cell from hazardous areas, Zone 0/20 and 1/21. The terminal can be connected in 4- or 6-wire technology. The ratio between the bridge voltage U. D, and the supply voltage U. R, is determined in 16-bit resolution, and the load value is calculated as a process value. Apart from automatic self-calibration (can be deactivated), additional functions such as Tara and Freeze as well as dynamic filters are integrated.
Technology: | resistor bridge, strain gauge |
Sensor types: | resistor bridge, strain gauge |
Number of inputs: | 1, for 1 resistor bridge in full bridge technology |
Bridge input resistance: | 300 Ω…1.5 kΩ |
Measuring range UD: | max. -18…+18 mV |
Measuring range UREF: | max. -12…+12 V |
Internal resistance: | > 25 kΩ (UR, differential), > 1 MΩ (UD, differential) |
Input filter limit frequency: | typ. 3.6 kHz (-3 dB, low pass) |
Conversion time: | typ. 1.6 ms |
Resolution: | 24 bit, 32 bit presentation |
Filter: | 50 Hz, configurable |
Measuring error: | < ±0.5 % (relative to full scale value), self-calibration activ |
Power supply UV: | up to 12 V DC from power contacts, dependent on sensor |
Supply voltage electronics: | 24 V DC (via power contacts), ELX9560 power supply |
Current consumption power contacts: | depends on sensor, min. 20 mA |
Current consumption E-bus: | typ. 85 mA |
Supported nominal sensitivity: | all, parameter resolution: 0.01 µV/V; recommended: 0.5…3 mV/V |
Special features: | self-calibration, dynamic filters, Freeze, TwinSAFE SC |
Weight: | approx. 60 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/see documentation |
Approvals/markings: | CE, UL, ATEX, IECEx, cFMus |
Ex marking: | ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4 |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |