Article image ELX3312-0090

Beckhoff ELX3312-0090

ELX3312-0090 | 2-channel analog input terminal thermocouple/mV measurement, 2-wire connection, 16 bit, Ex i, TwinSAFE SC

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The ELX3312 analog input terminals allows the direct connection of thermocouples located in hazardous areas classified Zone 0/20 or 1/21. The circuitry of the ELX3312 can operate sensors with 2-wire technology. Linearisation is possible over the entire freely selectable temperature range. The error LEDs indicate a broken wire. Compensation for the cold junction is achieved through internal temperature measurement. Millivolt measurement is also possible with ELX3312.

Technical parameters

Technology: temperature measurement
Sensor types: thermocouples type K, J, L, E, T, N, U, B, R, S, C (default: type K)
Number of inputs: 2 (differential)
Connection method: 2-wire
Measuring range: depending on sensor type, default type K: -200…+1350 °C, voltage measurement: ±30…±100 mV, for further types and details see documentation
Resolution: 0.1 °C per digit
Measuring error: < ±0.3 % (relative to full scale value)
Internal resistance: typ. ≥ 10 kΩ (differential)
Input filter limit frequency: typ. 1 kHz; depending on sensor length, conversion time, sensor type
Conversion time: 10…5000 ms (adjustable, default: 270 ms)
Supply voltage electronics: 24 V DC (via power contacts), ELX9560 power supply
Current consumption power contacts: typ. 10 mA
Current consumption E-bus: typ. 70 mA
Special features: limit value monitoring, digital filter and characteristic curve linearisation integrated, TwinSAFE SC
Weight: approx. 60 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/see documentation
Approvals/markings: CE, UL, ATEX, IECEx, cFMus
Ex-Marking: ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m