EL1722
EL1722 | 2-channel digital input terminal 120…230 V AC
The EL1722 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. It is possible to connect 120 V/230 V AC actuators directly. The EtherCAT Terminal contains two channels that indicate their signal state by means of light emitting diodes. The EL1722 does not have any power contacts. This makes it possible to create individual potential groups. The voltage between input 1 and input 2 must not exceed 230 V AC.
Connection technology: | 2-wire |
Number of inputs: | 2 |
Nominal voltage: | 120/230 V AC |
“0“ signal voltage: | 0…40 V |
“1“ signal voltage: | 79…260 V |
Input current: | > 3 mA, typ. 6 mA |
Input filter: | typ. 10 ms |
Distributed clocks: | – |
Switching times: | 10 ms |
Current consumption power contacts: | – |
Current consumption E-bus: | typ. 110 mA |
Electrical isolation: | 500 V (E-bus/mains voltage); 3750 V AC, 1 min. |
Bit width in the process image: | 2 inputs |
Configuration: | no address or configuration setting |
Special features: | no power contacts |
Weight: | approx. 60 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all ESxxxx terminals |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |