101218030
PROTECT-SELECT-SK
2 safety relay outputs. 2 sichere Relaisausgänge. 4 optionale Meldeausgänge. 4 optional signalling outputs. 4 sichere Halbleiterausgänge. No programming skills required. 4 safety semi-conductor outputs. Einfache und flexible Parametrierung. Simple and flexible parameter setting. Fehler- und Statusmeldung im Klartext. Keine Programmierkenntnisse erforderlich. Error and status messages in plain text. Mehrsprachige Menüführung per Farbdisplay. Multilingual menu navigation via colour display. Replaces up to 8 safety-monitoring modules up to. PL e / SIL 3. Ersetzt bis zu 8 Sicherheitsrelais bis PL e / SIL. 3. 18 safe inputs for the redundant inquiry of all, common safety sensors. 18 sichere Eingänge zur redundanten Abfrage von, allen gängigen Sicherheitssensoren
EAN (European Article Number): | 4030661445397 |
Product name: | PROTECT SELECT |
Terminal (mechanical): | Removable screw terminals |
Material of the contacts, electrical: | Tin |
Weight: | 300 g |
Short circuit detection: | Yes |
Wire breakage detection: | Yes |
Short-circuit recognition: | Yes |
Removable Terminals: | Yes |
Start input: | Yes |
Feedback circuit: | Yes |
Automatic reset function: | Yes |
Reset edge detection: | Yes |
Start-up test: | Yes |
Earth connection detection: | Yes |
Integral System Diagnostics, status: | Yes |
Integrated Display, Supply Voltage: | Yes |
Number of pulse outputs (test pulse output): | 3 |
Number of relay outputs (1-channel): | 2 |
Number of fail-safe analogue inputs: | 2 |
Number of digital fail-safe inputs: | 14 |
Number of digital fail-safe in-/outputs: | 4 |
Number of fail-safe digital outputs: | 4 |
Number of signalling outputs: | 4 |
Performance Level: | e |
Control category to EN13849: | 4 |
Diagnostic Coverage (DC) Level: | 90 |
PFH-value: | 1.78 x 10⁻⁸ /h |
Safety Integrity Level (SIL): | 3 |
Mission Time: | 20 Year(s) |
Common Cause Failure (CCF), minimum: | 65 |
Hardware fault tolerance (HFT): | 1 |
Demand rate: | high or continuous |
Safe Failure Fraction (SFF), minimum: | 90 |
Performance Level: | e |
Control category: | 4 |
Safety Integrity Level (SIL): | 3 |
Performance Level: | d |
Control category: | 2 |
Safety Integrity Level (SIL): | 2 |
Performance Level: | d |
Control category: | 2 |
Safety Integrity Level (SIL): | 2 |
Performance Level: | e |
Control category: | 4 |
Safety Integrity Level (SIL): | 3 |
Mounting: | Snaps onto standard DIN rail to EN 60715 |
Mechanical life, minimum: | 10,000,000 Operations |
Terminal Connector: | rigid or flexible |
Terminal designations: | IEC 61131-2 IEC/EN 60947-1 |
Tightening torque of Clips: | 0.6 Nm |
Width: | 52.5 mm |
Height: | 100 mm |
Depth: | 118 mm |
Ambient temperature, minimum: | -25 °C |
Ambient temperature, maximum: | +55 °C |
Storage and transport temperature, minimum: | -25 °C |
Storage and transport temperature, maximum: | +75 °C |
Relative humidity, minimum: | 15 % |
Relative humidity, maximum: | 90 % |
Note (Relative humidity): | non-condensing |
Resistance to vibrations to EN 60068-2-6: | 10 … 57 Hz, amplitude 0.75 mm |
Rated impulse withstand voltage: | 0.8 kV 4 kV |
Voltage type: | DC (direct current) |
Operating voltage: | 24 V |
Operating voltage, minimum: | 21.6 VDC |
Operating voltage, maximum: | 26.4 VDC |
Current consumption at 24V, maximum: | 500 mA |
No-load current: | 500 mA |
Required rated short-circuit current to EN 60947-5-1: | 1,000 A |
Switching frequency, maximum: | 0.1 Hz |
Current consumption of the safety inputs at 24V: | 6 mA |
Rated operating current (safety outputs): | 700 mA |
Safety output: | short-circuit proof, p-type / n-type (Q0/0N and Q1/1N) short-circuit proof, p-type (Q2 und Q3) |
Current leakage: | 2 mA |
Operating current (diagnostic output): | 100 mA |
Note (applications): | Safety sensor Guard system Emergency-Stop button Pull-wire emergency stop switches Safety light curtain |
Operating voltage, minimum: | 21.6 VDC |
Operating voltage, maximum: | 26.4 VDC |
Current consumption at 24V, maximum: | 500 mA |
No-load current: | 500 mA |
Required rated short-circuit current to EN 60947-5-1: | 1,000 A |
Switching frequency, maximum: | 0.1 Hz |
Switching thresholds of fail-safe inputs: | -3 V … 2 V (LOW) 18 V … 28.8 V |
Current consumption of the safety inputs at 24V: | 6 mA |
Rated operating current (safety outputs): | 700 mA |
Safety output: | short-circuit proof, p-type / n-type (Q0/0N and Q1/1N) short-circuit proof, p-type (Q2 und Q3) |
Current leakage: | 2 mA |
Operating current (diagnostic output): | 100 mA |
Note (applications): | Safety sensor Guard system Emergency-Stop button Pull-wire emergency stop switches Safety light curtain |
ECCN: | |
Ursprungsland: | DE |
EAN: | |
Gewicht: | 0,30 kg |
Länge: | 0,00 m |